Unitronics I/O Expansions

Expand your system with a wide variety of Unitronics’ remote or local I/O expansion modules, An I/O expansion adapter allows you to connect various local or remote I/O combinations to Vision series PLCs.

The M90/M91PLCs support local modules only.

Unitronics EXF-RC15

The EXF-RC15 is a digital high-speed Remote IO Expansion Module that enables your Vision™ controllers to handle a great variety of motion-control related applications.
Easily configured and programmed via Visilogic, the EXF-RC15 offers 9 digital inputs, 4 digital transistor outputs, and 2 relay outputs. Three inputs can be set via wiring and software to function as high-speed counters. The four transistor outputs may function as high-speed PWM/PTO outputs.

EXF-RC15 (2)

EX-A2X

Local expansion adapter—used to link between the PLC and up to 8 expansion modules (no. of I/Os may vary according to model). Supports both 12/24VDC.

 

EX-RC1

Remote expansion adapter—used to link between Vision PLCs and I/O expansion modules via CANbus. Multiple adapters may be connected to a single PLC, with up to 8 module to each adapter (no. of I/Os may vary according to model). Supports both 12/24VDC.

 

IO-AI4-AO2

24VDC (power supply)
4 Analog inputs, 12 bit, 0-10V, 0-20mA, 4-20mA
2 Analog outputs, 12 bit + sign, 0-10V, 0-20mA, 4-20mA.

IO-AO6X

24VDC (power supply)
6 Isolated Analog outputs, 12 bit, 0-10V, 0-20mA, 4-20mA.

IO-PT400

4 PT100 / NI100 / NI120 inputs,
Range PT100: -50°C : 460°C (-58°F : 860°F)
Range NI100: -50°C : 232°C (-58°F : 449°F)
Range NI120: -50°C : 172°C (-58°F : 341°F)
12 bit.

IO-PT4K

4 PT1000 / NI1000 inputs
Range PT1000: -50oC ÷ 460oC, (-58oF ÷ 860oF)
Range NI1000: -50oC ÷ 232oC, (-58oF ÷ 449oF)
12 bit

 

IO-ATC8

8 Thermocouple/Analog inputs (T/C: J, K, T, B, E, N, R, S, 0.1° resolution.

Analog: 12/14 bit, 0-10V, 0-20mA, 4-20mA).

IO-LC1

12/24VDC (power supply)
1 Loadcell / Strain gauge input. Voltage range: ±20mV, ±80mV, execution: AC/DC
1 Digital pnp input
2 setpoint pnp outputs
(* Not supported by the M90 line).

IO-LC3

12/24VDC (power supply)
3 Loadcell / Strain gauge inputs. Voltage range: ±20mV, ±80mV, execution: AC/DC
1 Digital pnp input
2 setpoint pnp outputs
(* Not supported by the M90 line).

IO-D16A3-RO16

24VDC
16 Digital pnp/npn inputs, including 2 High-speed counters
3 Analog inputs, 10 bit, 0-20mA, 4-20mA
16 Relay outputs

 

IO-D16A3-TO16

24VDC
16 Digital pnp/npn inputs, including 1 High-speed counter
3 Analog inputs, 10 bit, 0-20mA, 4-20mA
16 Transistor pnp/npn outputs, including 1 High-speed output

EX-D16A3-RO8

24VDC
16 Digital pnp/npn inputs, including 2 High-speed counters
3 Analog inputs, 10 bit, 0-20mA, 4-20mA
8 Relay outputs
Adapter not required.

EX-D16A3-TO16

24VDC
16 Digital pnp/npn inputs, including 1 High-speed counter
3 Analog inputs, 10 bit, 0-20mA, 4-20mA
16 Transistor pnp/npn outputs, including 1 High-speed output
Adapter not required.

IO-DI8-TO8

24VDC
8 Digital pnp/npn inputs, including 1 High-speed counter
8 Transistor pnp outputs.
Supports Fast-response (in conjunction with Vision PLCs)

 

IO-DI8-RO8

24VDC
8 Digital pnp/npn inputs, including 1 High-speed counter
8 Relay outputs.

IO-DI8-RO4

24VDC
8 Digital pnp/npn inputs, including 1 High-speed counter
4 Relay outputs.

IO-DI16

24VDC
16 Digital pnp/npn inputs, including 1 High-speed counter.

IO-TO16

12/24VDC
16 Transistor pnp outputs.

IO-RO8

24VDC (power supply)
8 Relay outputs.

IO-RO16

24VDC (power supply)
16 Relay outputs.

EX90-DI8-RO8

24VDC
8 Digital pnp inputs, including 1 High-speed counter
8 Relay outputs
(This unit is housed in an open casing. Only one EX90 can be connected per PLC, as a single expansion module; EX-A1 adapter not required).

IO-DI8-TO8-L

8 Digital pnp/npn inputs, including 1 High-speed counter
8 Transistor pnp outputs.

IO-DI8-RO8-L

12VDC
8 Digital pnp/npn inputs, including 1 High-speed counter
8 Relay outputs.

IO-DI8-RO4-L

12VDC
8 Digital pnp/npn inputs, including 1 High-speed counter
4 Relay outputs.

IO-RO8-L

12VDC (power supply)
8 Relay outputs.

IO-RO16-L

12VDC (power supply)
16 Relay outputs.

IO-DI8ACH

110/220 VAC
8 AC Inputs

IO-AI8

I/O Expansion Module with 8 analog inputs
0÷10V/0÷20mA